WHAT WE DO

Smoke and Fire Curtain Applications

Every deployable curtain application maps to a wall type in IBC Chapter 7 — smoke partition, smoke barrier, fire partition, fire barrier, or fire wall. The wall type on the life safety plan determines the test standard the opening protective must meet: UL 10B 20-minute without hose stream for smoke partitions, UL 10D and UL 1784 for smoke barriers and fire partitions, UL 10B with the ASTM E2226 hose stream for fire barriers and fire walls. The exception is elevator hoistway smoke containment — not a wall type, but hoistway opening protection evaluated to ICC AC 77. Below, all six, with the code driver and matched products for each.

FIND THE RIGHT PRODUCT

Opening in Smoke Partition

IBC §710UL 10B 20 MIN · NO HOSEASTM E136ASTM E84

Smoke-only separation — no fire-resistance rating. Non-hose-stream-tested draft and smoke curtains for atria, escalator wells, and floor openings classified as smoke partitions.

Opening in Smoke Barrier Wall

IBC §709UL 10DUL 1784

1-hour fire-resistance-rated, smoke-resistant construction. Opening protectives tested to UL 10D and UL 1784 — hose stream not required.

Opening in Fire Partition Wall

IBC §708UL 10DUL 1784ASTM E2226

1-hour rated: corridors, elevator lobbies, dwelling unit separations. UL 10D and UL 1784 tested; the Hose Stream line covers openings where ASTM E2226 applies.

Opening in Fire Barrier Wall

IBC §707UL 10BUL 1784ASTM E2226

1–3 hour rated: shafts, exit enclosures, occupancy separations. Hose stream tested per ASTM E2226 with y-axis deployment and retraction.

Opening in Fire Wall

IBC §706UL 10BUL 263ASTM E2226IBC 903.1.1

2–4 hour structural separation creating separate buildings. Hose-stream-tested curtains close openings in and between fire walls; moveable fire wall assemblies deploy on the x, y, and z axes per UL 263.

MATCHED PRODUCTS

Elevator Hoistway Smoke Containment

ICC AC 77IBC 3006 / 3008

Not an IBC Chapter 7 wall type — hoistway opening protection evaluated to ICC AC 77. Fire rating and hose stream: not required.

MATCHED PRODUCTS

SPEC ASSISTANCE