UL CERTIFICATION
UL 10D vs UL 10B: What the Standards Actually Mean
UL 10D is the standard for fire protective curtains — deployable fabric assemblies rated for fire exposure. UL 10B is the fire test for fire shutters and door assemblies and includes the hose stream test (ASTM E2226), where the assembly is blasted with a fire hose after burning. A curtain that passes UL 10D protects against smoke and fire; an assembly that passes UL 10B with hose stream survives fire plus the mechanical shock of firefighting. Fire barrier walls typically demand the hose stream test. Smoke partitions do not.
UL 10D
What UL 10D requires
Fire exposure testing for deployable curtains, paired with UL 1784 air leakage for smoke.
Fire exposure
RATED FIRE PROTECTIVE CURTAIN
Air leakage — UL 1784
SMOKE CONTAINMENT
Hose stream — ASTM E2226
NOT REQUIRED
UL 10B
What UL 10B adds
The hose stream test — and why fabric-only curtains cannot pass it (our Steel-Tex® shutters do).
Fire exposure
FIRE TEST OF FIRE SHUTTERS AND DOOR ASSEMBLIES
Hose stream — ASTM E2226
BLASTED WITH A FIRE HOSE AFTER BURNING
Fabric-only curtains
CANNOT PASS — STEEL-TEX® SHUTTERS DO
Which standard does your opening need?
The IBC Chapter 7 wall type on the life safety plan determines the test standard — the exception is elevator hoistway smoke containment, which requires UL 1784 air leakage only. Each row links to its full application.
| OPENING TYPE | CODE | REQUIRED STANDARD | PRODUCT LINE |
|---|---|---|---|
| Smoke Partition | IBC §710 | UL 10B 20 MIN — NO HOSEASTM E136 · ASTM E84 | SD60® smoke & draft curtain line |
| Smoke Barrier | IBC §709 | UL 10D + UL 1784HOSE STREAM NOT REQUIRED | SD60GS® / SD240GS® / SD240A® rated curtains |
| Fire Partition | IBC §708 | UL 10D + UL 1784ASTM E2226 WHERE HOSE STREAM APPLIES | Rated curtains · Hose Stream where required |
| Fire Barrier | IBC §707 | UL 10B + ASTM E2226HOSE STREAM TESTED | Hose Stream shutter line |
| Fire Wall | IBC §706 | UL 10B + ASTM E2226UL 263 FOR MOVEABLE FIRE WALLS | Hose Stream / Dual Hose Stream lines |
| Elevator Hoistway | ICC AC 77 | UL 1784NO FIRE RATING · NO HOSE STREAM REQUIRED | ESC / SD60GS® hoistway line |